12 Micro830 48 Point Programmable Controllers

Publication 2080-IN005B-EN-P - April 2014

Control Drawing for Class 1 Division 2 Applications

Hazardous Location
Class 1 Division 2,
Groups A, B, C, and D

Non-Hazardous Location

Micro800
Controller

USB Port

J3

V

max

= 5V DC

I

max

= 500

μA

L

i

= 1

μH

C

i

= 120 pF

Any associated apparatus with
Universal Serial Bus (USB) connection

USB Port

V

oc

, I

sc

, L

a

and C

a

to be determined per

Capacitance and Inductance Values
table

Capacitance and Inductance Values

Nonincendive

Equipment

Associated Apparatus

V

max

(or U

i

)

≥ V

oc

or V

t

(or U

o

)

I

max

(or L

i

)

≥ I

sc

or I

t

(or I

o

)

C

i

+ C

cable

≤ C

a

(or C

o

)

L

i

+ L

cable

≤ L

a

(or L

o

)

Capacitance and Inductance of the field wiring from the nonincendive equipment to
the associated apparatus shall be calculated and must be included in the system
calculations as shown in the table above.

Where the cable capacitance and inductance per foot are not known, the following
values shall be used: C

cable

= 60 pF/ft, L

cable

= 0.2

μH/ft.

Wiring method must be in accordance with ANSI/NFPA70.