Remove the unit – Rockwell Automation 2500 SecureConnect Units for CENTERLINE 2500 Low Voltage Motor Control Centers User Manual
Page 12
12
Rockwell Automation Publication 2500-IN005B-EN-P - April 2012
SecureConnect Units for CENTERLINE 2500 Low Voltage Motor Control Centers
Remove the Unit
Follow this procedure to remove the SecureConnect unit.
1. Turn the main disconnect switch to the OFF/O position.
2. Move the flange handle from the Connected to the Test position.
a. Press and hold the black button on the front of the door.
b. Start moving the handle to the right while releasing the black button.
c. Move handle until it clicks into the Test position.
3. Move the flange handle from the Test to the Disconnected position.
a. Press and hold the black button on the front of the door.
b. Start moving the handle to the right while releasing the black button.
c. Move handle until it clicks into the Disconnected position.
4. Unlock and open the unit door.
IMPORTANT
Listen for the handle to click into place. Then, verify that the handle is locked
into place by trying to move the handle back and forth.
IMPORTANT
Listen for the handle to click into place. Then, verify that the handle is locked
into place by trying to move the handle back and forth.
• Control and Network connections: ON
• Line and Load Power: OFF
Test
Turn Off
Circuit Breaker
Press
Black Button
Move Handle
Flange Handle in
the Test Position
Black Button
• Control and Network connections: OFF
• Line and Load Power: OFF
Disconnected
Press
Black Button
Move Handle
Black Button
Turn Off
Circuit Breaker
Flange Handle in the
Disconnected Position