beautypg.com

Remove the unit – Rockwell Automation 2500 SecureConnect Units for CENTERLINE 2500 Low Voltage Motor Control Centers User Manual

Page 12

background image

12

Rockwell Automation Publication 2500-IN005B-EN-P - April 2012

SecureConnect Units for CENTERLINE 2500 Low Voltage Motor Control Centers

Remove the Unit

Follow this procedure to remove the SecureConnect unit.

1. Turn the main disconnect switch to the OFF/O position.

2. Move the flange handle from the Connected to the Test position.

a. Press and hold the black button on the front of the door.
b. Start moving the handle to the right while releasing the black button.
c. Move handle until it clicks into the Test position.

3. Move the flange handle from the Test to the Disconnected position.

a. Press and hold the black button on the front of the door.
b. Start moving the handle to the right while releasing the black button.
c. Move handle until it clicks into the Disconnected position.

4. Unlock and open the unit door.

IMPORTANT

Listen for the handle to click into place. Then, verify that the handle is locked
into place by trying to move the handle back and forth.

IMPORTANT

Listen for the handle to click into place. Then, verify that the handle is locked
into place by trying to move the handle back and forth.

Control and Network connections: ON
Line and Load Power: OFF

Test

Turn Off

Circuit Breaker

Press

Black Button

Move Handle

Flange Handle in
the Test Position

Black Button

Control and Network connections: OFF
Line and Load Power: OFF

Disconnected

Press

Black Button

Move Handle

Black Button

Turn Off

Circuit Breaker

Flange Handle in the
Disconnected Position