Rockwell Automation 2711-NL1 PanelView 550 Backlight Lamp Replacement User Manual
Page 3

40061-182-01(C)
3
To replace the backlight lamp:
1. Turn off the power to the PanelView terminal.
Important: Turning off the power provides a standard reset. Changing the
lamp with power applied may result in an unintentional reset.
2. Remove lamp access cover.
3. Disconnect backlight lamp cable connector. The connector has a locking tab
which you must press to separate the connector.
4. Remove lamp from mounting clip. Avoid contact with the infrared filter.
5. If your terminal has a metal lamp clip (see illustration on previous page), you
will need to replace it with the new lamp base provided in this kit. Replace the
lamp base by removing the two screws that secure the lamp base and re-install
the new base.
6. Insert the new lamp into holder.
7. Connect lamp cable to connector. Make sure that cable is firmly held and in the
proper position.
8. Replace lamp access cover.
9. Apply power to the terminal.
10. If new lamp does not illuminate, refer to the PanelView Operator Terminal User
Manual for instructions on lamp control from the front panel.
Access Cover
PanelView 550
Touch & Keypad, Keypad Only versions
PanelView 550
Touch Only Versions
Access Cover
!
ATTENTION: Lamp may be hot. Allow lamp to cool before
proceeding to avoid personal injury.
!
ATTENTION: Do not touch the reflecting surface or halogen
bulb when handling new lamp to avoid damaging lamp.