Certifications, Environmental specifications – Rockwell Automation 2085-IQ16_IQ32T 24V DC 16 and 32 Sink/Source Input Modules User Manual
Page 14
![background image](/manuals/580363/14/background.png)
14 Micro800 16-point and 32-point 12/24V Sink/Source Input Modules
Publication 2085-IN001A-EN-P - September 2012
Derating Curve for 2085-IQ16
EFT/B immunity
IEC 61000-4-4:
±2 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certification (when product
is marked)
(1)
Value
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and
Canada. See UL File E334470
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
(1)
See the Product Certification link at
for Declaration of Conformity, Certificates, and
other certification details.
Environmental Specifications
Attribute
Value
30
26.4
30°C
65°C
Input voltage (V)
45302
Temp