Rockwell Automation 2080-LC50-24AWB_24QBB_24QVB_24QWB Micro850 24-Point Programmable Controllers Installation Instructions User Manual
Page 18
18 Micro850 24 Point Programmable Controllers
Publication 2080-IN007B-EN-P - April 2014
Relay Contacts Ratings
Maximum Volts
Amperes
Amperes
Continuous
Volt-Amperes
Make
Break
Make
Break
120V AC
15 A
1.5 A
2.0 A
1800V A
180V A
240V AC
7.5 A
0.75 A
24V DC
1.0 A
1.0 A
28V A
125V DC
0.22 A
Environmental Specifications
Attribute
Value
Temperature,
operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)
Temperature,
surrounding air, max
65 °C (149 °F)
Temperature,
non-operating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Shock,
non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
DIN mount:: 25 g
PANEL mount: 35 g
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF
immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz