Specifications – Rockwell Automation 2080-LC50-24AWB_24QBB_24QVB_24QWB Micro850 24-Point Programmable Controllers Installation Instructions User Manual
Page 14
![background image](/manuals/580266/14/background.png)
14 Micro850 24 Point Programmable Controllers
Publication 2080-IN007B-EN-P - April 2014
Specifications
General Specifications
Attribute
2080-LC50
-24AWB
-24QWB
-24QVB
-24QBB
Number of I/O
24 (14 inputs, 10 outputs)
Dimensions
HxWxD
90 x 158 x 80 mm
(3.54 x 6.22 x 3.15 in.)
Shipping
weight,
approx.
0.423 kg (0.933 lb)
Wire size
Wiring
category
(1)
2 – on signal ports
2 – on power ports
2 – on communication ports
Wire type
Use Copper Conductors only
Terminal
screw torque
0.4…0.5 Nm (3.5…4.4 lb-in.) using a 0.6 x 3.5 mm flat-blade screwdriver.
Note: Use a handheld screwdriver to hold down the screws at the side.
Input circuit
type
12/24V sink/source (standard)
24V sink/source (high-speed)
Output circuit
type
Relay
24V DC sink
(standard and
high-speed)
24V DC source
(standard and
high-speed)
Power
consumption
28 W
Power supply
voltage range
20.4…26.4V DC Class 2, or
Limited Voltage Limited Current Source (LVLC)
I/O rating
Input 120V AC
16 mA
Output 2 A, 240V
AC, 2A, 24V DC
Input 24V, 8.8 mA
Output 2 A, 240V
AC
2A, 24V DC
Input 24V, 8.8 mA
Output 24V DC, Class 2, 1 A per
point (Surrounding air temperature
30 °C)
24V DC, Class 2, 0.3 A per point
(Surrounding air temperature 65 °C)
Min
Max
Solid and
Stranded
0.2 mm
2
(24 AWG)
2.5 mm
2
(14 AWG)
rated @ 90 °C
(194 °F ) insulation max