Specifications, Instance 102 - configuration input / output, Input – Rockwell Automation 1799ER-IQ10XOQ10 Dual-Port EtherNet Embedded I/O Board with 10 Inputs/ Outputs User Manual
Page 16: Output

16 Dual-Port EtherNet Embedded I/O Board with 10 Inputs/ 10 Outputs
Publication 1799ER-IN001B-EN-P - May 2013
Specifications
5
Group 0 Input OFF_ON Delay Filter (High Byte)
6
Group 0 Input ON_OFF Delay Filter (Low Byte)
7
Group 0 Input ON_OFF Delay Filter (High Byte)
8
Reserved
IV_G0
IA_G0
FV_G0
FA_G0
9
Reserved (pad)
CRN = Configuration Revision Number. Value is 0 after power-on reset and after completely closing the
connection. Value is 1 when the module is configured. Once a module is configured, the only way to
change its configuration is to close the connections to it or use the override value of 0.
FA_Gx = Fault Action Group x. 0 = Apply Fault Value, 1 = Hold Last State
IA_Gx = Idle Action Group x. 0 = Apply Idle Value, 1 = Hold Last State
FV_Gx = Fault Value Group x. 0= Off, 1=On
IV_Gx = Idle Value Group x. 0= Off, 1=On
Input Filter values = 0, 1000, 2000, 4000, 8000, or 16000 microseconds.
Input
Attribute
Value
Inputs per block
10 sinking or sourcing, Type 1 + compatible
Off-state voltage
5V DC max
Off-state current
1.5 mA max
On-state voltage
10...30V DC
On-state current
2...11 mA
Output
Attribute
Value
Outputs per block
10 sinking or sourcing, 0.5A, short circuit protected, pilot duty
Output auxiliary voltage
10...30V DC
On-state voltage drop
250 mV max
Instance 102 - Configuration Input / Output
Config Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0