Phase-loss relay, Figure 15.5 phase loss relay – Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual
Page 179
Publication 2364P-5.01 December 1999
Installation
Phase-Loss Relay
An NRU in the parallel configuration will be equipped with a phase-
loss relay, which is used to indicate phase loss, phase unbalance,
undervoltage, phase reversal conditions in the 3-phase AC line. The
relay has NO/NC contacts, connections for a reset control, and
jumper connections for setting undervoltage and phase unbalance
tolerances. The relay LEDs indicate AC line conditions and change
of state in the relay.
Figure 15.5
Phase Loss Relay
The system voltage dial should be set to the nominal AC line voltage,
and a restart delay of 0.0 minutes is recommended. Typically, the
normally-open contacts (terminals 1 and 2) will be wired to the fault
circuitry in the NRU, and the normally-closed contacts (terminals 3
and 4) will be wired to TB1-3 and TB1-4 for customer connection.
N O C ontacts
NC Con tacts
M an ual
Reset
C om m on
Un dervoltag e
Respon se C urves
Phase Un balanc e
Respon se Cu rves
C ustom er-S up plied
R eset S w itc h
1
2
3
4
5
6
7
8
9
10
U1
U2
I1
I2
Ph ase A
Voltage
Ph ase B
Voltage
Ph ase C
Voltage
L1
L2
L3
Term inal D efin ition s
T o TB 1-3,
TB 1-4
To Fau lt
Circ uitry
1
6
2
7
3
8
4
9
5
10
A
B
C
CONTACTS
TRANSFERRED
PHASE
REVERSAL
PHASE
LOSS
PHASE
UNBALANCE
UNDER
VOLTAGE
RESTART
DELAY
0.0
.25
.50
1.0
2.0
3.0
4.0
5.0
SYSTEM
VOLTAGE