Phase-loss relay, Figure 15.5 phase loss relay – Rockwell Automation 2364P Parallel DC Bus Supply Config. User Manual

Page 179

background image

Publication 2364P-5.01 December 1999

Installation

15-7

Phase-Loss Relay

An NRU in the parallel configuration will be equipped with a phase-
loss relay, which is used to indicate phase loss, phase unbalance,
undervoltage, phase reversal conditions in the 3-phase AC line. The
relay has NO/NC contacts, connections for a reset control, and
jumper connections for setting undervoltage and phase unbalance
tolerances. The relay LEDs indicate AC line conditions and change
of state in the relay.

Figure 15.5
Phase Loss Relay

The system voltage dial should be set to the nominal AC line voltage,
and a restart delay of 0.0 minutes is recommended. Typically, the
normally-open contacts (terminals 1 and 2) will be wired to the fault
circuitry in the NRU, and the normally-closed contacts (terminals 3
and 4) will be wired to TB1-3 and TB1-4 for customer connection.

N O C ontacts

NC Con tacts

M an ual

Reset

C om m on

Un dervoltag e

Respon se C urves

Phase Un balanc e
Respon se Cu rves

C ustom er-S up plied
R eset S w itc h

1

2

3

4

5

6

7

8

9

10

U1

U2

I1

I2

Ph ase A

Voltage

Ph ase B

Voltage

Ph ase C

Voltage

L1

L2

L3

Term inal D efin ition s

T o TB 1-3,

TB 1-4

To Fau lt

Circ uitry

1

6

2

7

3

8

4

9

5

10

A

B

C

CONTACTS
TRANSFERRED

PHASE
REVERSAL

PHASE
LOSS

PHASE
UNBALANCE

UNDER
VOLTAGE

RESTART
DELAY

0.0

.25

.50

1.0

2.0

3.0

4.0

5.0

SYSTEM
VOLTAGE