Ground-Fault Detection Option

The parallel configuration may include the optional ground-fault
detector. When configured properly, this detector will indicate the
ground voltage on the door-mounted meter, and will energize the
relay (with NO/NC contacts) in the event of an excessive ground
voltage.

To configure the ground-fault detection relay, wire terminals TB2-1
and TB2-2 across the power transformer grounding resistor (in
accordance with system schematics and transformer manufacturer
specifications). Terminals TB1-7 and TB1-8 can be wired to an
appropriate monitoring device, if desired.

Figure 15.3
Ground-Fault Detection (Wiring)

1

2

1

2

7

8

7

8

TB 2

TB 1

150

10

12

2

4

G ro und-F au lt De te ction

M e ter-R elay O ptio n (VM 2)

To M on itoring

D evice

Pow e r Transform er

G ro unde d-W ye Se co nda ry