Rockwell Automation 1799-D16U16BAGL 16 Input/16 Output Digital and 2 Input/2Output Analog User Manual
Page 27
16 Input/16 Output Digital and 2 Input/2 Output Analog Embedded I/O Boards 27
Publication 1799-IN011A-EN-P - February 2007
Network Status Indicator (Labeled NS)
DeviceLogix Status Indicator (Labeled DL)
I/O State Indicators (Labeled Inputs and Outputs)
Analog Input Indicators
Analog Output Indicators
Indication
Status
None
Not on-line
Green
Blinking Green
On-line/no connections
Solid Green
On-line/connected
Red
Blinking Red
Connection timed out
Solid Red
Failed communication: a duplicate node address exists or
module is at the wrong communication rate
Indication
Status
None
Logic disabled
Green
Solid Green
Logic enabled
Blinking Green
Local forces applied and local logic enabled
Color
Indication
Status
None
Input or output point off
Yellow
Solid Yellow
Input or output point on
Color
Indication
Status
None
No power or calibration started
Green
Blinking Green
Calibration in process
Solid Green
Normal operation
Red
Blinking Red
Open wire or out of range
Solid Red
No AD communications
Color
Indication
Status
None
No power or calibration started
Green
Blinking Green
Calibration in progress
Solid Green
Normal operation
Red
Blinking Red
Open wire or out of range