Additional Parameters
Parameter
Description
AI Low Scaling
Analog input low scaling value or low engineering units.
AI High Scaling
Analog input high scaling value or high engineering units.
AI Digital Filter
Controls digital filter time constant.
AI Alarm (Low/High Low)
Low/High High)
Control alarm status when input exceed alarm threshold.
AI Input Range
Defines type and range of input signal. Controls way of calibration.
AI Enable Alarm Latch
Controls latch of alarm status until a reset latch service is issued.
AI Disable Alarms
Controls function of alarm.
AI Notch Filter
Controls sample rate of A/D converter.
AI Update Rate
Assigns the rate at which the inputs are sampled by firmware.
AO Fault Value
Controls output value during communication fault.
AO Idle Value
Controls output value during idle or program mode.
AO Low Scaling
Analog output low scaling value or low engineering units.
AO High Scaling
Analog output high scaling value or high engineering units.
AO Low Clamp
The lowest value of the output. If the output value is set below this
value, the output will be set to the low clamp value.
AO High Clamp
The highest value of the output. If the output value is set above this
value, the output will be set to the high clamp value.
AO Output Range
Defines type and range of output signal. Controls way of calibration.
AO Fault State
Controls the output choices during a communication fault.
AO Idle State
Controls the output choices during idle or program mode.
AO Enable Alarm Latch
Controls latch of alarm status until a reset latch service is issued.
AO Disable Alarms
Controls function of alarm.