Mount the kinetix 350 drive – Rockwell Automation 2097-Vxxx Kinetix 350 Single-axis EtherNet/IP Servo Drive Installation Instruction User Manual
Page 5
Kinetix 350 Single-axis EtherNet/IP Servo Drives 5
Rockwell Automation Publication 2097-IN008D-EN-P - July 2013
Mount the Kinetix 350 Drive
Follow these steps to mount the drive.
1. Observe these clearance requirements when mounting the drive to the panel.
IMPORTANT
Mount the module in an upright position as shown. Do not mount the module on
its side.
Drive
Cat. No.
Dimensions A
mm (in.)
2097-V31PR0-LM
185 (7.29)
2097-V31PR2-LM
2097-V32PR0-LM
230 (9.04)
2097-V32PR2-LM
2097-V32PR4-LM
2097-V33PR1-LM
185 (7.29)
(1)
(1)
If you are using an AC line filter, add
50 mm (2 in.).
2097-V33PR3-LM
2097-V33PR5-LM
2097-V33PR6-LM
230 (9.04)
2097-V34PR3-LM
185 (7.29)
(1)
2097-V34PR5-LM
2097-V34PR6-LM
230 (9.04)
A
• Additional clearance and different hole patterns are required for side
mount and rear mount AC line filters. See the table and
step 2
for more
details.
• Additional clearance is required depending on the other accessory
items installed.
• Additional clearance is required for the cable and wires connected to
the top, front, and bottom of the drive.
• An additional 150 mm (6.0 in.) is required when the drive is mounted
adjacent to noise sensitive equipment or clean wire ways.
Refer to
page 6
for Kinetix 350 drive dimensions.
25 mm (1.0 in.) Clearance
for Airflow and Installation
25 mm (1.0 in.) Clearance
for Airflow and Installation
3 mm (0.12 in.)
Side Clearance
3 mm (0.12 in.)
Side Clearance