Power wiring requirements – Rockwell Automation 2097-Vxxx Kinetix 350 Single-axis EtherNet/IP Servo Drive Installation Instruction User Manual

Page 11

background image

Kinetix 350 Single-axis EtherNet/IP Servo Drives 11

Rockwell Automation Publication 2097-IN008D-EN-P - July 2013

Shunt Resistor and DC Bus (BC) Pinout

Motor Power (MP) Pinout

Safe Torque-off (STO) Pinout

The Kinetix 350 drive ships with safe torque-off enabled. Connect safe torque-off inputs to a
safety circuit, or install motion-allowed jumpers to obtain motion. Refer to the Kinetix 350
Single-axis EtherNet/IP Servo Drive User Manual, publication

2097-UM002

, for details.

Power Wiring Requirements

Wire must be copper with 75

°C (167 °F) minimum rating. Phasing of main AC power is

arbitrary and earth-ground connection is required for safe and proper operation.

BC Designator

Description

Signal

+

Positive DC bus and shunt resistor

+

+

+

SH

Shunt resistor

SH

Negative DC bus

MP Designator

Description

Signal

PE

Protective earth (ground)

PE

W

Motor power out

W

V

Motor power out

V

U

Motor power out

U

STO Pin

Description

Signal

1

+24V DC output from the drive

+24V DC control

2

+24V DC output common

Control COM

3

Safety status

Safety Status

4

Safety input 1 (+24V DC to enable)

Safety Input 1

5

Safety common

Safety COM

6

Safety input 2 (+24V DC to enable)

Safety Input 2

IMPORTANT

The National Electrical Code and local electrical codes take precedence over the values and
methods provided.