beautypg.com

Ground the terminal, Connect devices – Rockwell Automation 2711C-xxxx PanelView Component HMI Terminals Installation Instructions User Manual

Page 25

background image

PanelView Component HMI Terminals 25

Publication 2711C-IN001H-EN-P - July 2014

4. Apply 24V DC power to the terminal.

Ground the Terminal

PanelView Component devices have a functional earth terminal that you must connect to a low-impedance
earth ground. The functional earth connection is on the power input terminal block. The negative power
terminal is not internally connected to earth ground.

The functional earth terminal wiring requires a minimum wire gauge.

Connect Devices

Use these cables for connecting devices to PanelView Component terminals.

ATTENTION: The functional earth connection to ground is mandatory. This connection is
required for noise immunity, reliability, and Electromagnetic Compliance (EMC) with the
European Union (EU) EMC directive for CE-mark conformance.

Functional Earth Wire Specifications

FE Symbol

Wire Type

Wire Gauge

Terminal Screw Torque

Stranded or solid

Cu 90 °C (194 °F)

2.08…3.31 mm

2

(14…12 AWG)

0.45…0.56 Nm (4…5 lb-in)

Cables for PanelView Component Terminals

Cat. No.

Description

For Use With

2711C-CBL-UU02

USB-A host to USB-B device cable, 2 m (6.56 ft)

C200, C300, C400, C600, C1000

2711P-CBL-EX04

Ethernet crossover CAT5 cable 4.3 m (14 ft)

C400, C600, C1000

2711C-RCSD

USB to SD adapter with secure digital (SD) card

C200, C300, C400, C600, C1000

DC+

Functional
Earth Ground
to Ground Bus

DC-

44887