Mount the new terminal in the cutout adapter plate – Rockwell Automation 2711P-RAT12E2 Adapter Kit for PanelView 1200/1200E Touch Screen Terminal Cutout User Manual
Page 6
6 Adapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout
Publication 2711P-IN014D-EN-P - July 2007
6. Using the 12 nuts with flat and lock washers, fasten the cutout adapter plate
to the panel.
Tighten the washers until the gasket is slightly compressed against the front
of the panel.
7. Using the torque wrench, tighten the nuts to not more than 1.1 Nm (10 lb-in)
to maintain the NEMA Type 4X rating.
Do not overtighten.
Mount the New Terminal in the Cutout Adapter Plate
Follow these steps to mount the new terminal into the cutout adapter plate.
1. Insert the new terminal into the adapter plate cutout until the terminal
gasket is flush with the front of the adapter plate.
2. Install the six mounting clips according to the installation instructions
provided with the new terminal.
The ends of the clips slide into the slots on the terminal.
3. Tighten the screws on the mounting clips by hand until the gasket seal
contacts the mounting surface uniformly.
4. Using the torque wrench, tighten the screws on the mounting clips to the
specified torque rating provided in the installation instructions of the new
terminal.
Do not overtighten.
Mounting Slot
Adapter Plate
Screw Driver Slot
Mounting
Stud
Mounting
Clip
Mounting
Clip
Screw-
driver