Specifications, Specifications 23 – Rockwell Automation 1791ES-IB16 CompactBlock Guard I/O EtherNet/IP Safety Modules User Manual
Page 23
CompactBlock Guard I/O EtherNet/IP Safety Modules 23
Publication
1791ES-IN001C-EN-P - September 2009
Specifications
Guard I/O EtherNet/IP Safety Module - 1791ES-IB8XOBV4, 1791ES-IB16
Attribute
Value
Safety Input
Input types
Current sinking
Voltage, on-state Input, min
11V DC
Current, on-state Input, min
3.3 mA
Voltage, off-state input, max
5V DC
Current, off-state, max
1.3 mA
IEC 61131-2 (input type)
Type 3
Pulse Test Output
Output type
Current sourcing
Pulse test output current
0.7 A per output
8 A total module @ 40 °C (104 °F)
6 A total module @ 60 °C (140 °F) for 1791ES-IB8XOBV4
module (see temperature versus current derating)
8 A total module @ 60 °C (140 °F) for 1791ES-IB16 module
Residual voltage, max
1.2V
Output leakage current, max
0.1 mA
Short circuit protection
Yes
Current, max
(when used to control
muting lamp)
25 mA
Current, max (to avoid fault when used as a muted lamp
output)
Current, min
(when used to control
muting lamp)
5 mA
Current, min (at which fault indication is generated when
used as a muted lamp output)