Network Activity Indicator
State
Status
Off
No link established
Flashing green/off
Transmit or receive activity
Steady green
Link established
Safety Input Status Indicator
State
Status
Description
Recommended Action
Off
Safety input
off or module
being
configured
The safety input is off or the
module is being configured.
Turn the safety input on or
wait for the module to be
configured.
Solid
yellow
Safety input
on
The safety input is on.
None.
Solid red
Fault detected
A fault in the external wiring
or input circuit detected.
Check configuration, field
wiring, and devices. If no
problem found, replace
module.
Flashing
red
Partner fault
detected
A fault in the partner input
circuit of a dual input
configuration detected.
Check the field wiring and
verify your configuration for
the partner circuit. If no
problem found, replace
module.