4 POINT I/O™ RTD and Isolated Thermocouple Input Modules

Publication 1734-IN011H-EN-E - February 2014

North American Hazardous Location Approval

ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials (for example, aluminum, plastic) that can corrode,
oxidize, or are poor conductors can result in improper or intermittent grounding.
Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and
use end-anchors appropriately.

ATTENTION: To comply with the CE Low Voltage Directive (LVD), this
equipment must be powered from a source compliant with the Safety Extra Low
Voltage (SELV) or Protected Extra Low Voltage (PELV).

The following information applies when
operating this equipment in hazardous
locations:

Informations sur l’utilisation de cet
équipement en environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for
use in Class I Division 2 Groups A, B, C, D, Hazardous
Locations and nonhazardous locations only. Each product is
supplied with markings on the rating nameplate indicating
the hazardous location temperature code. When combining
products within a system, the most adverse temperature code
(lowest "T" number) may be used to help determine the
overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec des marquages
sur sa plaque d'identification qui indiquent le code de
température pour les environnements dangereux. Lorsque
plusieurs produits sont combinés dans un système, le code
de température le plus défavorable (code de température le
plus faible) peut être utilisé pour déterminer le code de
température global du système. Les combinaisons
d'équipements dans le système sont sujettes à inspection
par les autorités locales qualifiées au moment de
l'installation.

EXPLOSION HAZARD
• Do not disconnect equipment unless power

has been removed or the area is known to be
nonhazardous.

• Do not disconnect connections to this

equipment unless power has been removed
or the area is known to be nonhazardous.
Secure any external connections that mate
to this equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.

• Substitution of components may impair

suitability for Class I, Division 2.

• If this product contains batteries, they must

only be changed in an area known to be
nonhazardous.

RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que

l'environnement est classé non dangereux
avant de débrancher l'équipement.

• Couper le courant ou s'assurer que

l'environnement est classé non dangereux
avant de débrancher les connecteurs. Fixer
tous les connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.

• La substitution de composants peut rendre

cet équipement inadapté à une utilisation
en environnement de Classe I, Division 2.

• S'assurer que l'environnement est classé

non dangereux avant de changer les piles.