beautypg.com

Rockwell Automation 1734-IT2I, Series C Point I/O RTD and Isolated Thermocouple Input Module Installation Instructions User Manual

Page 17

background image

POINT I/O™ RTD and Isolated Thermocouple Input Modules 17

Publication 1734-IN011H-EN-E - February 2014

Indicator Status for Modules

Status

Description

Module status

Off

No power applied to device.

Green

Device operating normally.

Flashing green

Device needs commissioning due to missing, incomplete, or
incorrect configuration.

Flashing red

Recoverable fault.

Red

Unrecoverable fault occurred. Self-test failure present (checksum
failure, or ramtest failure at cycle power). Firmware fatal error
present.

Flashing red/green Device is in self-test mode.

Network status Off

Device is not online:

- Device has not completed dup_MAC-id test.

- Device not powered – check module status indicator.

Flashing green

Device is online but has no connections in the established state.

Green

Device is online and has connections in the established state.

Flashing red

One or more I/O connections are in timed-out state.

Red

Critical link failure – failed communication device. Device detected
error that prevents it from communicating on the network.

Flashing red/green Communication faulted device – the device has detected a

network access error and is in communication faulted state. Device
has received and accepted an Identity Communication Faulted
Request – long protocol message.

Channel status
status

Off

Module is in CAL mode.

Solid green

Normal operation is present with channel scanning inputs.

Flashing green

Channel is being calibrated.

Solid red

Major channel fault is present.

Flashing red

Channel is at end of range (over or under).