Rockwell Automation 1790-TXXXX CompactBlock LDX I/O Profibus Analog, RTD and Thermocouple User Manual
Page 28
28
Publication 1790-IN010B-EN-P - April 2003
4-Channel Input Thermocouple Base Block Specifications
1790P-T4T0
Inputs per module
4 channel, Thermocouple/mV Input
Input Range
+76.50mV
Sensors Supported
Sensor Type
Range
Scaling
Voltage 10V
-76.50 to +76.50mV
-7650 to +7650
Type B
300 to 1800°C
3000 to 18000
Type E
-270 to 1000°C
-2700 to 10000
Type J
-210 to 1200°C
-2100 to 12000
Type K
-270 to 1370°C
-2700 to 13700
Type R
-50 to 1768°C
-500 to 17680
Type S
-50 to 1768°C
-500 to 17680
Type T
-270 to 400°C
-2700 to 4000
Type N
-270 to 1300°C
-2700 to 13000
Resolution
16 bits, 0.1°C/bit or 0.1°F/bit (Thermocouple Sensors)
20bit Sigma-Delta modulation converter
Data Format
16 bit Integer (2’s compliment)
Module Scan Time
140ms/channel @ Notch Filter = 60Hz
Overall accuracy
0.2% Full scale @0°C-60°C
Settable Notch Filter
10Hz (default), 25Hz, 50Hz, 60Hz, 100Hz, 250Hz, 500Hz
Open Wire Detection
Out of range, open wiring
Cold Junction
Compensation Range
0 to 70°C
Input Impedance
5M ohm
General Specifications
PROFIBUS Power
Supply voltage - 24V dc nominal
Voltage range - 19.2-28.8V dc
Power dissipation - 1.2W maximum @ 28.8V dc
Field Power
Supply Voltage - 24Vdc nominal
Voltage Range - 21.6-26.4V dc (+10%)
Power Dissipation - 1.5W maximum @26.4V dc
Isolation
I/O to logic: photocoupler isolation
Isolation voltage: Type Test 1250V ac rms for 60 seconds
PROFIBUS to logic: non-isolated
Field power: non-isolated
Indicators
4 red/green I/O status
Wiring
Terminal block connector
screw torque: 7 inch pounds maximum
IMPORTANT: This module does not support any expansion modules.