4-Channel Input RTD Base Block Specifications
1790P-T4R0
Inputs per module
4 channel, RTD/Resistance Input
Input Range
1-625
Sensors Supported
Sensor Type
Degree
Counts
Resolution
Resistance 100m
Ω
1 to 625
Ω 10 to 6250 100mΩ
Resistance 10m
Ω
1 to 327
Ω 100 to
32700
10m
Ω
100ohm Pt/
α =0.00385
-200 to
+850°C
-2000 to
+8500
0.1°C
200ohm Pt/
α =0.00385
-200 to
+850°C
-2000 to
+8500
0.1°C
500ohm Pt/
α =0.00385
-200 to
+650°C
-2000 to
+6500
0.1°C
100ohm Pt/
α =0.003916 -200 to
+640°C
-2000 to
+6400
0.1°C
200ohm Pt/
α =0.003916 -200 to
+640°C
-2000 to
+6400
0.1°C
500ohm Pt/
α =0.003916 -200 to
+640°C
-2000 to
+6400
0.1°C
100ohm Nickel
-60 to
250°C
-600 to
2500
0.1°C
120ohm Nickel
-80 to
260°C
-800 to
2600
0.1°C
200ohm Nickel
-60 to
250°C
-600 to
2500
0.1°C
500ohm Nickel
-60 to
250°C
-600 to
2500
0.1°C
Resolution
16 bits across 625ohms, 0.1°C/bit or 0.1°F/bit (RTD Sensors)
20bit Sigma-Delta modulation converter
Data Format
16 bit Integer (2’s compliment)
Module Scan Time
8ms/channel @ Notch Filter = 60Hz
Overall accuracy
0.2% Full scale @0°C-60°C
Settable Notch Filter
10Hz (default), 25Hz, 50Hz, 60Hz, 100Hz, 250Hz, 500Hz
Open Wire Detection
Out of range, open wiring
Excitation Current
1mA
Input Impedance
5M ohm