beautypg.com

Processor/module compatibility, 6ć13 – Rockwell Automation 1771-DCM USER MANUAL 1771-DCM User Manual

Page 34

background image

Programming the 1771-DCM

Chapter 6

6Ć13

Your 1771–DCM must have the following revision (or later) for
compatible block transfer operation with your processor.

Processor Family

1771-DCM Revision

PLC-3

F

PLC-5

E

PLC-5/250

E

Data transfers would occur as follows when the supervisory processor is a
PLC–3:

Supervisory Processor

To

Local Processor

BTW Instruction Writes Data to the

1771-DCM from Binary File 3, Words

0 through 63

BTR Instruction Reads Data from the 1771-DCM

into Words 300 through 377

FB003:0000 Status Word (Zeroed)

FB003:0001 First Data Word

FB003:0002 Second Data Word

:

:

FB003:0063 Last Data Word

300 Status Word (Inserted by DCM)

301 First Data Word

302 Second Data Word

:

:

377 Last Data Word

Local Processor

To

Supervisory Processor

BTW Instruction Writes Data to the

1771-DCM from Words

200 through 277

BTR Instruction Reads Data from the 1771-DCM

into Binary File 2, Words 0 through 63

200 Status Word (Zeroed)

201 First Data Word

202 Second Data Word

:

:

277 Last Data Word

FB002:0000 Status Word (Inserted by DCM)

FB002:0001 First Data Word

FB002:0002 Second Data Word

:

:

FB002:0063 Last Data Word

Processor/Module Compatibility