beautypg.com

Rockwell Automation 1758-RTU202 Datasite Installation Instructions User Manual

Page 25

background image

DataSite Natural Gas Flow Meter and Remote Terminal Unit 25

Publication 1758-IN001C-EN-P - June 2011

EFT/B immunity

IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
±1 kV at 5 kHz on communications ports

Surge transient immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±1 kV line-earth(CM) on shielded ports
±1 kV line-earth(CM) on communications ports

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications

Certification (when product is
marked)

(1)

Value

C-UL-US

UL Listed Industrial Control Equipment
UL Listed Industrial Control Equipment for use in Canada
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File E10314

CE

Marked for all application directives

C-Tick

Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions

(1)

See the Product Certification link at

http://www.ab.com

for Declaration of Conformity, Certificates, and other certification

details.

Environmental Specifications

Attribute

Value