DataSite Natural Gas Flow Meter and Remote Terminal Unit 23
Publication 1758-IN001C-EN-P - June 2011
Voltage input impedance
100 k
Ω for 10V DC inputs
170
Ω for 20 mA inputs
Input Resolution
16-bit
Non-linearity
±0.1% of full scale
Overall accuracy
±0.1% of full scale at 25 °C
±0.3% of full scale over temperature range
Voltage Input Overvoltage
Protection
Continuous input must not exceed 160% of the rated range
Analog Outputs
Attribute
Description
D/A resolution ratio
16-bit
Power supply
Successive approximation
Output signal range
4…20 mA
Maximum load
Impedance
1000
Ω with 24V DC loop power
400
Ω with 12V DC loop power
Output type
Single ended regulation on positive side with common negative return
Isolation voltage
70V AC or 100V DC
Absolute accuracy
±0.2% (25 °C with 250
Ω load)
±0.5% (full temperature range, 0…1000
Ω load)
Response time
100 ms typical (10…90%)
Noise and ripple, max
0.04%
Transient protection
600 W
HART
Attribute
Description
Modulation
Frequency Shift Keying (FSK)
Logic 1 - 1200 Hz
Logic 0 - 2200 Hz
Data rate
1200 bps
Transmit level
500 mVp-p / 250
Ω
Receive sensitivity
120 mVp-p/ on
80 mVp-p/ off
Analog Inputs
Attribute
Description