Specifications – Rockwell Automation 1758-RTU202 Datasite Installation Instructions User Manual
Page 21

DataSite Natural Gas Flow Meter and Remote Terminal Unit 21
Publication 1758-IN001C-EN-P - June 2011
Specifications
General
Attribute
Description
Dimensions
213 x 133 x 56 mm
(8.375 x 5.25 x 2.20 in.)
Number of I/O
8 digital inputs
4 digital outputs
8 analog inputs
2 analog outputs
3 pulse inputs
Power supply voltage
12V DC, (-15%, +10%)
Heat dissipation, nominal
< 1.2 W
Power consumption
80…120 mA
Input circuit type
Current Sinking
Output circuit type
Current Sourcing (FET)
Terminal screw torque
0.8 Nm (7 in-lb)
North American temp code
T4
Wire size
0.34... 2.5 mm² (22...12 AWG) solid or stranded copper wire rated at
90 °C (194 °F ) or greater 1.2 mm (3/64 in.) insulation max
Pulse Input
Attribute
Description
Voltage range
12…24V DC
Off-state voltage
8V DC
Operating frequency
10 kHz with filters off
30 kHz with filters on
On-state current, min
5 mA
On-state current, nom
6 mA
On-state current, max
13.2 mA
Off-state leakage current
2.5 mA
Nominal impedance
2 k
Ω