Setting the ControlNet Network Address

Valid ControlNet network addresses are 1-99. Network address zero is reserved. Switch 1
controls the most significant decimal digit (the tens). Switch 2 controls the least significant
decimal digit (the ones). Figure 6 shows the location of the network address switches and an
example of switch settings for a network address of 15.

Figure 6 ControlNet Network Address Switches Set to 15

Follow these steps to set the ControlNet network address for the 1788-CN2FF.

1. Choose and set a network address.

2. Write the network address setting in the space provided on the CN2FF label.

3. Apply (or cycle) power to the CN2FF to enable the new network address.

4. Make the same address changes in your NI-FBUS configuration software.