Rockwell Automation 1788-CN2FF ControlNet to Foundation Fieldbus H1 Linking Device Installation Instructions User Manual
Installation instructions, Product overview
Publication 1788-IN051D-EN-P - February 2004
Installation Instructions
ControlNet-to-Foundation Fieldbus H1 Linking
Device
Catalog 1788-CN2FF
Product Overview
The ControlNet-to-Foundation Fieldbus H1 linking device (1788-CN2FF) connects a
ControlNet™ network with one or two F
OUNDATION
Fieldbus H1 (Fieldbus) networks.
Each H1 network consists of multiple Fieldbus devices. Each field device has one or more
function blocks. Each function block performs an elementary control function such as analog
input, analog output, discrete input, or discrete output. The ControlNet network consists of
controllers, such as PLC
®
processors, HMIs, drives, I/O devices, and so on. The
1788-CN2FF has three broad functions, supporting the following:
• closed-loop control
• configuration
• a redundant ControlNet network design
ATTENTION
The 1788-CN2FF module ships from the factory with
configuration switches set to “ON (RESET)”. With switches
“ON”, any configuration data would be reset on Power
interruption. Set the switches to “OFF (NORMAL)” after initial
power-up (to clean any Factory test configurations) but before you
configure the module with your application.
Remove power to the module before resetting configuration
switches. For more information on configuration refer
to Configuring the 1788-CN2FF Linking Device on page 9.
Document Outline
- ControlNet-to-Foundation Fieldbus H1 Linking Device
- Product Overview
- Important User Information
- Handling the 1788-CN2FF Module
- System Requirements
- 1788-CN2FF Hardware Description
- Configuring the 1788-CN2FF Linking Device
- Installing the 1788-CN2FF
- Removing the 1788-CN2FF
- Connecting Power
- Connecting to the ControlNet Network
- Setting the ControlNet Network Address
- Interpreting the LEDs: ControlNet Network Status
- Interpreting the LEDs: Module Status
- Connecting to the Fieldbus Network
- Device vs. Connection Clarifications
- Specifications
- Rockwell Automation Support