1757-FFLDC2, 1757-FFLDC4 - Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock)
0…60 °C (32…140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp
Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
5 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
15 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
ESD immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Emissions
CISPR 11
Group 1, Class A
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from
30…2700 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
900 MHz and 1890 MHz