Status Indicators
Use the information in the following table to interpret the status indicators.
Module Status Indicators
Indicator
Status
Description
H1
Off
The H1 channel is inactive.
Verify that the linking device is connected to the H1 network.
Flashing green The linking device H1 channel is active.
STATUS
(module)
Off
No power - Module does not have 24V DC power.
Flashing green Standby - Module not configured.
Solid green
Operational - Module operating correctly.
Flashing red
Minor fault - A recoverable fault has been detected.
Verify that the configuration is correct and consistent.
Solid red
Major fault - An unrecoverable fault has been detected.
Recycle power to the module. If this does not clear the fault,
replace the module.
WDOG
(watchdog)
Off
Normal operation.
Flashing red
Software fault.
Contact Rockwell Automation Technical Support.