22 ControlNet Foundation Fieldbus Linking Device
Publication
1757-IN022B-EN-P - August 2009
BATT
(battery)
Off
Normal operation.
Flashing red
Jumper is missing (or not seated on the two rightmost pins), or
the battery is low or dead.
(1)
NS
(network
status)
Off
Not powered.
Flashing green No connections to the Logix blocks in the controller or to the
Logix blocks in the linking device.
•
Verify physical connection by using the ControlNet
status indicators.
•
Verify that:
– the Logix block is downloaded to the controller (via
RSLogix 5000 software) and the linking device (via
RSFieldbus software).
– the Logix blocks’ slot numbers correspond in
RSLogix 5000 software and RSFieldbus software.
– the ControlNet network has been scheduled at least
once when using unscheduled connections to Logix
blocks and all Logix blocks using scheduled
connections have been scheduled.
Solid green
CIP Class 1 connections.
Flashing red
Connection timeout.
Verify that the linking device is connected to the ControlNet
network.
Solid red
Duplicate ControlNet node address.
Flashing red
and green
Self test.
MODE
Solid green
Linking device operational.
Flashing green Linking device out-of-service.
Verify that the Resource Block is set to Target Auto mode.
(1)
If the BATT status indicator remains on after the jumper is replaced, and power has been returned to
the linking device, contact Rockwell Automation Technical Support.
Module Status Indicators
Indicator
Status
Description