Input and Output Connections

Input and output wiring terminals are located on the front of the module, behind
the terminal cover. When you connect input and output devices, you must also be
concerned with the settings of dip switch SW1 (input connections), dip switch SW2
(output connections), and jumper JW1 (limit switch input connections). The
location and description of these are shown on pages 6 through 9.

1
2

3

4

5
6

7

0

A

B

Z

LS

FAULT

VDC

HSCE

OUT 1

OUT 3

OUT 0

OUT 2

A+

A-

Not

Used

Not

Used

Z+

Z-

LS

COM

DC

COM

B+

B-

LS

(24V dc)

LS

(12V dc)

LS

(5V dc)

VDC

OUT 0
OUT 1
OUT 2
OUT 3

DC COM

A+
B+

A-
B-

Not used

Not used

Z+

LS (24 VDC )

Z-

LS (12 VDC )

LS COM

LS (5 VDC )

OUTPUT

INPUT

Upper Retaining Screw Maximum
Torque = 0.7 to 0.9 Nm (6 to 8 in-lbs)

Lower Retaining Screw Maximum
Torque = 0.7 to 0.9 Nm (6 to 8 in-lbs)

Discrete Output Wiring
NOTE: V dc must be externally
supplied by the user. See
page 14 for output wiring.

Terminal Wiring

max. 2 wires per terminal

max. torque: 0.9 Nm (8 in-lbs)

Limit Switch and
Encoder Input Wiring

See pages 15 through 19 for
input wiring.