Set the Simulation Jumper
The module is shipped with the simulation jumper set in position POS G. This
setting allows input data to go above and below the range points. If the
simulation jumper is set to the POS E position, input data is clamped (does
not exceed) at range end points.
Set the Configuration
Jumpers
The module has configuration jumpers for determining the input type (voltage
or current) desired for each input. The module is shipped with the
configuration jumpers positioned for voltage mode.
Not that you can select either voltage or current for each input, but they must
all be either single-ended or all differential. Do not mix single-ended or
differential inputs on the module.
POS G
POS E
Simulation Jumper (shown in POS E
position). This position provides Clamped
Input Data at range end points.
Top edge of circuit board
1. Locate the simulation jumper at the top edge
of the module circuit board.
2. Using your fingers, slide the jumper of f the 2 posts.
3. Carefully position the jumper on 2 of the 3 posts that
correspond to your requirement.
Set the Simulation Jumper
Jumper
POS G
POS E
Simulation Jumper (shown in POS G
position). This position does not Clamp Input
Data at range end points.
Top edge of circuit board
Simulation
Simulation
Remove the four screws securing the side
cover to the module and remove the covers.
19805
11
Reposition the configuration jumpers associated with each
input channel according to your requirements
12
Y ou can mix voltage mode and current mode
settings on the module. Make sure that the entire
module is set for either single-ended or dif ferential.
Do not mix them.
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Channel
1 and 2
Channel
3 and 4
Channel
5 and 6
Channel
7 and 8
Channel
9 and 10
Channel
11 and 12
Channel
13 and 14
Channel
15 and 16
Differential
Single-ended
Voltage Mode
Differential
Current
Single-ended
Current
Differential or Single-ended (factory set)
Current Mode
Odd channel current
Even channel voltage
Even channel current
Odd channel voltage
Single-ended
Configuration
Jumpers
Reposition the cover and secure with the four
screws removed in step 1.
19813