beautypg.com

Rockwell Automation 1756-CNB ControlLogix ControlNet Bridge Module Installation Instructions User Manual

Page 27

background image

27

Publication 1756-IN571B-EN-P - April 2001

The following table summarizes the meanings of these states:

Cause

Action

Off

No power

None or power up.

Steady red

Faulted unit

Cycle power or reset unit
If fault persists, contact A-B
representative or distributor.

Alternating
red/green

Self-test

None

Alternating red/off Incorrect node configuration

Check network address and other
ControlNet configuration
parameters.

Cause

Action

Off

Channel disabled

Program network for redundant
media, if required.

Steady green

Normal operation

None.

Flashing green/off Temporary errors

None; unit will self-correct.

Node is not configured to go on
line

Make sure the configuration
manager node is present and
working and selected address is
not greater than selected UMAX

.

(1)

(1)

The configuration manager node is the node responsible for distributing ControlNet configuration data
to all nodes on the network.

Flashing red/off

Media fault

Check media for broken cables,
loose connectors, missing
terminators, etc.

No other nodes present on
network

Add other nodes to the network.

Flashing red/green Incorrect network configuration

Cycle power or reset unit.
If fault persists, contact A-B
representative or distributor.

and

A

B

or

A

B

This manual is related to the following products: