beautypg.com

Module status indicator and display, E 23, Ges 23 – Rockwell Automation 1756-CNB ControlLogix ControlNet Bridge Module Installation Instructions User Manual

Page 23: S 23 t, 23 t

background image

23

Publication 1756-IN571B-EN-P - April 2001

Module Status Indicator and Display

The Module Status Indicator LED and Module Status Display provide
diagnostic information as summarized in the following table.

Diagnostics

LED

Display

Cause

Action

Off

None

Module not communicating due
to a power supply fault or
internal fault.

1. Check the power supply.
2. Check the cable connectors.
3. Make sure the module is firmly

seated in the chassis.

4. If the indicator remains off,

replace the module.

Red

Msg
scrolls

(1)

Module’s network address is set
to 00, an invalid ControlNet
address, or 99, an invalid
ControlNet address if you are
using redundant control. See
footnote at end of table.

1. (Optional, see page 11.)

Turn chassis power supply off.

2. Remove the module from the

chassis.

3. Set the network address

switches to a unique address
(01-99, or 01-98 if redundant
control)

4. Install the module in the

chassis.

5. If off, turn chassis power

supply on.

BPA#
ERR

Module detected a different slot
address from that latched in at
power-up. Excessive noise on
the backplane causes this error.

Replace the chassis or module.

BPRX
ERR

Too many CRC errors being
generated by the multicast
backplane receiver, so the
backplane multicast receivers
have been shut off.

Replace the module.

BPIC

ERR

Hardware fault
within the module.

Replace the module.

CNIC

ERR

OK

This manual is related to the following products: