beautypg.com

Interpret status indicators, Troubleshooting, Interpret status indicators troubleshooting – Rockwell Automation 1771-IXHR INSTL INSTR HI RES TC/MV INPUT User Manual

Page 9

background image

High Resolution Thermocouple/Millivolt Input Module

9

Publication 1771-5.66 – October 1998

The front panel of the input module contains a green RUN indicator
and a red FAULT indicator. At power-up, the module momentarily
turns on both indicators as a lamp test, then checks for:

correct RAM operation

EPROM operation

EEPROM operation

a valid write block transfer with configuration data

If there is no fault, the red indicator turns off.

The green indicator comes on when the module is powered. It will
flash until the module is programmed. If a fault is found initially or
occurs later, the red fault indicator lights. The module also reports
status and specific faults (if they occur) in every transfer of data
(BTR) to the PC processor. Monitor the green and red indicators and
status bits in word 1 of the BTR file when troubleshooting your
module.

Possible module fault causes and corrective action are described in
the following table.

Indicators

Probable Cause

Recommended Action

RUN (green) off
FLT (red) off

No power to module

Check power to I/O chassis.
Cycle as necessary.

Possible short on module

Replace module.

LED driver failure

RUN (green) on
FLT (red) on

Microprocessor, oscillator or EPROM
failure

RUN (green) off
FLT (red) on

If immediately after power–up, indicates
RAM or EPROM failure.

1

If during operation, indicates possible
microprocessor or backplane interface
failure.

1

RUN (green)
blinking,
FLT (red) off

Power–up diagnostics successfully
completed.

Normal operation.

If LED continues to flash, and write block
transfers (BTW) cannot be accomplished,
you have a possible interface failure.

Replace module.

RUN (green) on
FLT (red) off

Normal operation

None

1

When red LED is on, the watchdog timer has timed out and backplane communications are terminated.

Your user program should monitor communication.

RUN

FLT

10528-I

Green RUN indicator

Red FAULT indicator

TC/MV

Module

For detailed troubleshooting
information, see chapter 7 of your
High Resolution
Thermocouple/Millivolt Input
Module User Manual
(publication
1771-6.5.131).

Interpret Status Indicators

Troubleshooting