10 ArmorBlock MaXum 2 Input Module Series B

Publication 1792D-IN019B-EN-P - September 2000

The following table describes network and module status indicators.

The following table describes logic status indicators.

The following table describes I/O status indicators.

For more information on indications see the Technical Data
publication 1792-TD001B-EN-P.

Net/Mod Status Indicator

Indication

Status:

Off

No power or auto bauding

Flashing Green/Off On line but not connected

Solid Green

On line, link OK, connected

Flashing Red

Recoverable fault - module configuration error

I/O connection fault - one or more I/O connections in the timed-out
state

Solid Red

Unrecoverable fault

Communication failure - duplicate node address present or incorrect
baud rate

Green to Red to Off At powerup only - LED test

Logic Status Indicators

State

Status

Off

Logic is disabled

Solid Green

Logic is enabled

Flashing Green

Local forces are applied and local logic is enabled

I/O Status Indicators

Function

Module Status Indicator

Point Indicator

1

Condition

Inputs

Green
Green
Module Status blink red
Module Status blink red

None
Yellow
Red
Blink red

No valid input
Valid input
short on input connection
Off-wire on input connection