4 - troubleshoot the processor system, Use the plc-5 processor status indicators, Chapter 4) – Rockwell Automation 1785-Lx0E,D178510.5 QUICK START ETHERNET PLC-9 User Manual
Page 19: Troubleshoot the processor system, Chapter
Publication 1785-10.5 - November 1998
Chapter
4
Troubleshoot the Processor System
Use the PLC-5 Processor
Status Indicators
Troubleshoot General Problems
Use the PLC-5 Processor
Status Indicators
(page 4-1)
1
BATT
PROC
FORCE
COMM
Indicator
Color
Description
Probable Cause
Recommended Action
BATT
Red
Battery low
Battery low
Replace battery within 10 days
Off
Battery is good
Normal operation
No action required
PROC
Green
(steady)
Processor is in run
mode and fully
operational
Normal operation
No action required
Green
(blinking)
Processor memory is
being transferred to
EEPROM
Red
(blinking)
Major fault
Run-time error
• Check major fault bit in status file
(S:11) for error definition
• Clear fault bit, correct problem,
and return to run mode
Red
(steady)
Major fault
• Processor memory
has checksum
error
• Memory module
error
• Internal
diagnostics have
failed
• Clear memory and reload program
• Check backplane switch settings
and/or insert correct memory
module
• Power down, reseat processor
and power up; then, clear
memory and reload your program.
Replace EEPROM with new
program; then, if necessary,
replace the processor
Off
Processor is in
program load or test
mode or is not
receiving power
Check power supply and
connections
BATT
PROC
FORCE
COMM