Connecting the devicenet wiring, Communicate with your armorblock module – Rockwell Automation 1792-IB16LP INSTL INSTR 16 INPUT MODULE User Manual
Page 5
5
ArmorBlock-LP 16 Input Module
Publication 1792-5.6 – September 1997
Connecting the DeviceNet Wiring
Connect DeviceNet wiring to the 5-pin mini-connector on the end of the
block. Connections are shown below.
1
2
3
DeviceNet Mini-Connector
Pin 1 = Drain (Bare)
Pin 2 = V+ (Red)
Pin 3 = V– (Black)
(View into pins)
4
5
Pin 4 = CAN–HI (White)
Pin 5 CAN–LO (Blue)
Note: Colors are
DeviceNet standard
Communicate with Your ArmorBlock Module
This ArmorBlock module’s I/O is exchanged with the master through a
poll, bit strobe or change of state connection.
When set for Polled, Bit Strobe, or change of state, the module consumes
and produces as follows:
Type of I/O
Connection
Consumes
Produces
Polled
0 Bytes
3 Bytes
Bit Strobe
0 Bytes
3 Bytes
Change of State
0 Bytes
3 Bytes
Polled device – a master initiates communication by sending its polled
I/O message to the ArmorBlock module. The 16 input module scans the
inputs and fault bit producing a response that reflects their status.
Change of state – productions occur when an input changes or an input
source voltage fault occurs. If neither has occurred within the “expected
packet rate,” a heartbeat production occurs. This heartbeat production
tells the scanner module that the ArmorBlock module is alive and ready
to communicate.
Bit Strobe device – a master initiates communication by sending its bit
strobe I/O message. All bit strobed devices then respond. The 16 input
module scans the inputs and fault bits, producing a response that reflects
their status.