beautypg.com

Connect the wiring to the armorblock module, Connecting the input wiring – Rockwell Automation 1792-IB16LP INSTL INSTR 16 INPUT MODULE User Manual

Page 4

background image

ArmorBlock-LP 16 Input Module

4

Publication 1792-5.6 – September 1997

Connect the Wiring to the ArmorBlock Module

This module uses quick disconnect, screw-on style connectors for:

I/O input wiring

the DeviceNet connector

30197–M

Eight 5-pin Input Micro-connectors

5-pin DeviceNet Mini-connector

A

B

A

B

A

B

A

B

A

B

A

B

A

B

A

B

1

2

3

4

56

7

8

Seven micro plugs are included with your module. Use these plugs to
cover and seal unused ports. Pinout diagrams for these connectors are
shown below.

!

ATTENTION: Make sure all connectors are securely
tightened to properly seal the connections against leaks and
maintain IP67 requirements.

Connecting the Input Wiring

Connect input wiring to the micro-connectors which screw into mating
connectors on the front of the block.

Make connections as shown below.

1

2

3

4

I/O Input Micro-Connector

Pin 1 = Sensor Source Voltage Positive

Pin 2 = Signal B

Pin 3 = Negative/Return

Pin 4 = Signal A

(View into socket)

5

Pin 5 = Ground

Use a splitter cable (or “Y” cable) to access signal B.