beautypg.com

Rockwell Automation 1762-Lxxxxx MicroLogix 1200 Programmable Controllers Installation Instructions User Manual

Page 22

background image

22 MicroLogix 1200 Programmable Controllers

Publication 1762-IN006C-EN-P - September 2009

Shock

Operating: 30G; 3 pulses each direction, each axis
Relay Operation: 7G
Non-Operating: 50G panel mounted (40G DIN Rail mounted); 3 pulses each direction, each
axis

Agency
Certification

• UL 508
• C-UL under CSA C22.2 no. 142
• Class I, Div. 2, Groups A, B, C, D

(UL 1604, C-UL under CSA C22.2 no. 213)

• CE/C-Tick compliant for all applicable directives

Electrical/EMC

The controller has passed testing at the following levels:

• IEC1000-4-2: 4 kV contact, 8 kV air, 4 kV indirect
• IEC1000-4-3: 10V/m, 80 to 1000 MHz, 80% amplitude modulation, +900 MHz keyed

carrier

• IEC1000-4-4: 2 kV, 5 kHz; communications cable: 1 kV, 5 kHz
• IEC1000-4-5: communications cable 1 kV galvanic gun

I/O: 2 kV CM (common mode), 1 kV DM (differential mode)
AC Power Supply: 4 kV CM (common mode), 2 kV DM (differential mode)
DC Power Supply: 500V CM (common mode), 500V DM (differential mode)

• IEC1000-4-6: 10V, communications cable 3V

Terminal Screw
Torque

0.791 Nm (7 in-lb) rated

(1)

Do not allow the total load power consumed by the 5V dc, 24V dc, and sensor power outputs to exceed 12W.

(2)

Do not allow the total load power consumed by the 5V dc, 24V dc, and sensor power outputs to exceed 16W.

Refer to the MicroLogix 1200 User Manual for system validation worksheets.

Description

1762-

L24AWA,
L24AWAR

L24BWA,
L24BWAR

L24BXB,
L24BXBR

40AWA,
40AWAR

L40BWA,
L40BWAR

L40BXB,
L40BXBR