beautypg.com

Block transfer read format – Rockwell Automation 1771-IFF/A,D17716.5.116 FAST ANALOG INPUT MODULE User Manual

Page 64

background image

7-2

Publication 1771Ć6.5.116 - May 1996

When a BTR length of 0 is programmed, the 1771-IFF/A will
respond with the 1771-IFE series A module default length of 20.

The bit/word description for the block transfer read of the fast analog
input module is described below.

Table 12.A

BTR Word Format for the Fast Analog Input Module

Word

Decimal Bit

(Octal Bit)

Description

Word 1

Bit 00

Power up bit (PU) - Used by the module to tell the processor that it is

alive but not yet configured. It is a key element in the application

program.

Bit 01

Out of range bit (OR) - This bit is sent to tell the processor that one

or more channels are either over or under range.

1

Bit 02

Invalid scaling bit (IS) - This bit reports that the scaling is somehow

invalid. Usually, both values are equal or minimum is greater than

maximum when this bit comes on. Can also be an invalid filter value.

Bit 03

Real time sample fault bit (RTS) - This bit is set if the module is

configured for RTS and a block transfer read has not occurred within

the user-programmed period.

Bit 04

Calibration status bit (CS) - When calibrating the module, this bit will

be cleared if the calibration was successful. If the bit is set, an

incorrect voltage/current was applied, or offset and gain calibrations

were attempted simultaneously.

Bit 05

EEPROM status bit (EE) - This bit is set if an error occurs saving

calibration data to nonvolatile memory. If this bit is set at powerup, the

data from the EEPROM did not pass the checksum and no calibration

values are used.

Bit 06

Hardware fault (HF) - When this bit is set, the dc/dc converter fuse

has blown. Digital logic will continue to operate.

Bits 07-15

(07-17)

Not used.

Word 2

Bits 00-15

(00-17)

Underrange bits for each channel. Bit 00 for channel 1, bit 01 for

channel 2, etc.

1

These bits are set (1) at approximately the input

range limits selected from Table 12.B.

Word 3

Bits 00-15

(00-17)

Overrange bits for each channel. Bit 00 for channel 1, bit 01 for

channel 2, etc. These bits are set (1) at approximately the input range

limits selected from Table 12.B.

Word 4

Bits 00-15

(00-17)

Polarity bits - Set when input is less than zero. Bit 00 for channel 1,

bit 01 for channel 2, etc.

Word 5 thru 20

Input values - Word 5 for channel 1, word 6 for channel 2, etc.

Word 21

Bits 00-15

(00-17)

Offset calibration results bits - Each bit represents a channel. After

a calibration BTW has been sent, the module confirms calibration by

echoing back the channels that were calibrated during the offset

calibration BTW. In differential mode, channels 09 thru 16 are zero.

Block Transfer Read

Format