Input type data format – Rockwell Automation 1771-IFF/A,D17716.5.116 FAST ANALOG INPUT MODULE User Manual

Page 53

background image

6-3

Publication 1771Ć6.5.116 - June 1996

Input Voltage and Current Ranges for the Fast Analog Input Module

Nominal Voltage or

Current Range

Corresponding 4ĆDigit BCD

Output Range

Corresponding 12ĆBit

Binary Output Range

Voltage or

Current Per Bit

+1 to +5V

0000 to +4095

0000 to + 4095

0.98mV

0 to 5V

0000 to +4095

0000 to +4095

1.22mV

Ć5 to +5V

Ć4095 to +4095

Ć4095 to +4095

1.22mV

Ć10 to +10V

Ć4095 to +4095

Ć4095 to +4095

2.44mV

0 to +20mA

0000 to +4095

0000 to +4095

.0049mA

+4 to +20mA

0000 to +4095

0000 to +4095

.0039mA

Ć20 to +20mA

Ć4095 to +4095

Ć4095 to +4095

.0049mA

Note:

Voltage and current input ranges are selectable on a per channel basis.

Select single-ended or differential inputs using the designated bit in
the configuration file. Inputs to a particular module must be all
single-ended or all differential. Set BTW word 3, bit 08 (bit 10 octal)
as shown below.

Selecting SingleĆended or Differential Inputs

Decimal Bit 8 (Octal Bit 10)

Input type

1

differential inputs

0

singleĆended inputs

Dec. Bits

15 14 13 12

11

10 09

08

07 06 05 04 03 02 01 00

Description

Octal Bits

17 16 15 14

13

12 11

10

07 06 05 04 03 02 01 00

Description

Write Word 3

Real Time Sampling

Data

Format

Input

Type

Digital Filter

Real time sampling, data format, input

type and digital filter

You must indicate what format will be used to read data from your
module. Typically, you select BCD with PLC-2 processors, and 2’s
complement binary with PLC-3 and PLC-5 processors. See
Appendix C for details on data format. You use BTW word 3, bits
09-10 (11-12 octal) to set the data format.

Selecting the Data Format

Decimal Bit 10

(Octal Bit 12)

Decimal Bit 09

(Octal Bit 11)

Data Format

0

0

BCD

0

1

two's complement binary, data first

1

0

two's complement binary

1

1

signed magnitude binary

Chapter

Appendix C

Input Type

Data Format