ArmorBlock LP2 8 Sinking Input/ 8 Output Module

Publication 1792D-5.42 - July 1999

Output Power and DeviceNet Cable

Refer to the DeviceNet Cable System Planning and Installation Manual,
publication DN-6.7.2, for more information on output power and
DeviceNet cables for your application.

Communicate with Your ArmorBlock LP2 I/O Module

This ArmorBlock module’s I/O is exchanged with the master through a
polled, change of state, or cyclic connection.

The module consumes and produces I/O data as follows:

Cyclic - allows configuration of the block as an I/O client. The block will
produce and consume its I/O cyclically at the rate configured.

Polled - a master initiates communication by sending its polled I/O
message to the module. The 8 input/8 output module consumes the
message, updates outputs, and produces a response. The response has input
data and the status of the Auxiliary power.

Change of state - productions occur when an input changes. If no input
change occurs within the expected packet rate, a heartbeat production
occurs. This heartbeat production tells the scanner that the I/O module is
alive and ready to communicate. Consumption occurs when data changes
and the master produces new output data to the I/O module.

Refer to the table below for the word/bit definitions.

Type of I/O Connections

Consumes

Produces

Cyclic

1 Byte

2 Bytes

Polled

1 Byte

2 Bytes

Change of State

1 Byte

2 Bytes

Bit

07

06

05

04

03

02

01

00

Produces 0

I7

I6

I5

I4

I3

I2

I1

I0

Produces 1

ISC

OPWR

RSVD

RSVD

RSVD

RSVD

RSVD

RSVD

Consumes 0

O7

O6

O5

O4

O3

02

01

00

Where: I = Input, ISC = Input Short Circuit, OPWR = Output Power (Auxiliary Power),
RSVD = Reserved, O = Output,