8 Input / 8 Output Module - Cat. No. 1792D-8BT8LP

Sinking Input Specifications

Max

Min

Inputs per block

8- 3 wire or dry contact PNP devices or 4 -4 wire
PNP devices

Sensor Source Current (per input)

50mA

-

On-state Voltage

25V dc

10V dc

On-state Current

10mA

2mA

Off-state Voltage

5V dc

-

Off-state Current

-

1.5mA

Sourcing Output Specifications

Max

Min

Outputs per block

8 sourcing outputs labeled O0, O1, O2, and O3

Output Auxiliary Voltage

30V

10V

On-state Voltage Drop

1V

-

On-state Current

0.3A

-

Off-state Leakage

1.5mA

-

Module Current (all outputs)

2.4A

-

Surge Current - for 10 ms,
repeatable every 2s

0.6A

-

General Specifications

Indicators

Network Status - red/green
Module Status - red/green
Auxiliary Power - green
Point LED - yellow

Communication Rate

• 125Kbps @ 500 meters (1600 feet) for thick

cable, flat media length 375 meters (1230 feet)

• 250Kbps @ 200 meters (600 feet) for thick

cable, flat media length 150 meters (492 feet)

• 500Kbps @ 100 meters (330 feet) for thick

cable, flat media length 75 meters (246 feet)

DeviceNet Power: Voltage

Current

25V dc max
125mA (no sensors)
500mA (full load)