4

ArmorBlock LP2 8 Sinking Input/ 8 Output Module

Publication 1792D-5.42 - July 1999

Connect the Input/Output Cord Sets to the LP2 Module

This module uses 5 pin micro (12mm) style PCB mounted connectors.

Eight micro caps cover the connectors on your module. Remove the caps
and connect your cord sets to the appropriate ports. This product has two
input or outputs per I/O connector. Use a “Y” splitter cable for access to all
I/O connections. For more information on these cables, see the Product
Data guide, publication 1792-2.1.

Use the micro caps to cover and seal unused ports. A pinout diagram for
the connectors is shown below.

1

5

3

4

2

41452

Input Micro-Connector

(View into Sockets)

Pin 1 Sensor Source Voltage

Pin 2 Input B

Pin 3 Return Logic Ground

1

Pin 4 Input A

Pin 5 Not Used

1.

Logic Ground is approximately 0.4V above DeviceNet V-measured at the module.

1

5

3

4

2

Output Micro-Connector

(View into Sockets)

Pin 1 Not Used

Pin 2 Output B

Pin 3 Auxiliary Power Ground

Pin 4 Output A

Pin 5 Not Used