Module status indicator – mod – Rockwell Automation 1732E-XXXX Ethernet/IP 24Vdc 16 Input Modules User Manual
Page 17

ArmorBlock 16-Point EtherNet/IP Module, Series A 17
Publication
1732E-IN002B-EN-E - February 2011
Module Status Indicator – MOD
Flashing
red
Connection time out
One or more connections
have timed out.
Reset connections to the
module.
Red
Duplicate IP
The module has detected
that its IP address is
already in use.
Resolve the IP address
conflict.
Flashing
red/green
Self-test in
progress
The module is performing
a powerup self-test.
None
State
Status
Description
Recommended Action
Off
Not powered
There is no power applied to
the device.
Apply power to the device.
Flashing
red/green
LED powerup
test
The module is performing a
powerup self-test.
None
Green
Module
operational
The module is operating
normally.
None
Flashing
red
Minor fault
The module has one of the
following recoverable
faults:
•
Firmware (NVS) update.
•
IP Address switches have
changed.
•
Check your configuration
and cycle power.
•
If a firmware update is in
progress, wait for it to
complete.
•
Verify that IP address
switches are set to the
desired value.
Solid red
Critical fault
The module has one of the
following unrecoverable
faults:
•
Self-test failure (checksum
failure or ramtest failure at
powerup).
•
Firmware fatal error.
Cycle power to the module.
If that does not fix the fault,
contact your Rockwell
Automation representative.
The module may need to be
replaced.
State
Status
Description
Recommended Action