Environmental specifications, General specifications – Rockwell Automation 1734-OA4, Series C POINT I/O 120/220V AC Output Module Installation Instructions User Manual
Page 19
POINT I/O 120/220V AC Output Module 19
Publication 1734-IN009E-EN-E - March 2013
Thermal dissipation, max
1734-OA2 – 6.8 BTU @ @ 264V AC
1734-OA4 – 11.9 BTU @ @ 264V AC
Isolation voltage
240V (continuous), Reinforced Insulation
Type tested @ 3250V DC for 60 s, field-side to system
External AC power supply
voltage, nom
120/220V DC @ 60 Hz
External AC power supply
voltage range
85...264V DC @ 27...63 Hz
Dimensions, approx., HxWxD
56.0 x 12.0 x 75.5 mm
(2.21 x 0.47 x 2.97 in.)
Wiring category
(1)
1 – on signal ports
Wire size
Determined by installed terminal block
Weight, approx.
30.9 g (0.068 lb)
Pilot duty rating
DC 14 pilot duty
North American temp code
T4
IEC temp code
T4
Enclosure type rating
None (open-style)
Keyswitch position
8
(1)
Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publicatio
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...55 °C (-4...131 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Shock):
-40...85 °C (-40...185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% noncondensing
General Specifications
Attribute
Value