POINT I/O 120/220V AC Output Module – 1734-OA2, 1734-OA4, Series C
Attribute
Value
Outputs per module
1734-OA2 – 2 nonisolated, sourcing
1734-OA4 – 4 nonisolated, sourcing
On-state voltage range, min
74V AC
On-state voltage range, nom
120/220V AC
On-state voltage range, max
264V AC
On-state voltage drop, max
1.0V @ 0.75 A
On-state current, min
10 mA per channel
On-state current, max
750 mA per channel
For 1734-OA4, 750 mA per output, 2.0 A max per module
Off-state leakage, max
2.7 mA @ 264V AC
Output current rating
1734-OA2 – 1.5 A (2 channels @ 0.75 A each)
1734-OA4 – 2.0 A (750 mA per output, 2.0 A max per module)
Product temperature versus
current derating
1734-OA2
1.5 A max per module @ 50 °C (122 °F)
Derate linearly 13% to 1.3 A max per module @ 55 °C (131 °F)
1734-OA4
2.0 A max per module @ 45°C (113 °F)
Derate linearly 30% to 1.4 A max per module @ 55 °C (131 °F)
Surge current
16 A for 100 ms, repeatable every 10 s
Delay time, max
(1)
Off to On
On to Off
(1)
Off-on delay is time from a valid output on signal to output energization. On-off delay is time from a valid output off
signal to output deenergization.
1/2 cycle
1/2 cycle
General Specifications
Attribute
Value
Terminal base screw torque
0.8 Nm (7 lb-in.)
Module location
1734-TB, 1734-TBS, 1734-TOP, or 1734-TOPS wiring base assembly
POINTBus current, max
75 mA @ 5V DC
Power dissipation, max
1734-OA2 – 2 W @ 264V AC
1734-OA4 – 3.5 W @ 264V AC