Communicate with your module – Rockwell Automation 1734-OA4, Series C POINT I/O 120/220V AC Output Module Installation Instructions User Manual

Page 15

background image

POINT I/O 120/220V AC Output Module 15

Publication 1734-IN009E-EN-E - March 2013

Communicate with Your Module

POINT I/O modules send (consume) and receive (produce) messages. These messages are
mapped onto the processor’s memory. This POINT I/O output module consumes 1 Byte
of output data (scanner Tx). It does not produce data (scanner Rx).

Refer to the following default data map tables.

Default Data Map for 1734-OA2

7

6

5

4

3

2

1

0

Produces (scanner Rx)

No produced data

Consumes (scanner Tx) Not used

Ch1

Ch0

Channel state

Where: 0 = Off, 1 = On

Default Data Map for 1734-OA4

7

6

5

4

3

2

1

0

Produces (scanner Rx)

No produced data

Consumes (scanner Tx) Not used

Ch 3

Ch 2

Ch1

Ch0

Channel state

Where: 0 = Off, 1 = On