Compact High-density Analog Current Input Module 23
Publication 1769-IN085A-EN-P - August 2008
Specifications
Compact High Density Analog Current Input Module - 1769-IF16C
Attribute
Value
Dimensions (HxWxD), approx.
118 mm x 87 mm x 35 mm
Height including mounting tabs is 138 mm (5.43 in.)
4.65 in. x 3.43 in. x 1.38 in.
Height including mounting tabs is 138 mm (5.43 in.)
Weight, approx.
(with carton)
281 g (0.62 lb)
Temperature, storage
-40 °C…85 °C (-40 °F…185 °F)
Temperature, operating
0 °C…60 °C (32 °F…140 °F)
Operating humidity
5% …95% non-condensing
Operating altitude
2000 m (6561 ft)
Vibration
Operating: 10…500 Hz, 5 g, 0.030 in. peak-to-peak
Shock
Operating: 30 g, 11 ms panel-mounted
(20 g, 11 ms DIN rail-mounted)
Non-operating: 40 g panel-mounted
(30 g DIN rail-mounted)
Bus current draw, max
190 mA @ 5V DC
70 mA @ 24V DC
Heat dissipation
4 total Watts (The Watts per point plus the minimum Watts with
all points energized.)
Module OK status indicator
On: The module has power, has passed internal diagnostics, and is
communicating over the bus.
Off: Any of the above is not true.
System power supply distance rating
The module may not be more than 8 modules away from the
system power supply.
Recommended cable
Belden 8761 (shielded)
Vendor I.D. code
1
Product type code
10
Product code
47
Input words
22
Output words
2
Configuration words
98